{"product_id":"abb-ai835a-3bse051306r1-analog-input","title":"ABB AI835A 3BSE051306R1 Analog Input","description":"\u003cp\u003eThe \u003cstrong\u003eABB AI835A\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003e3BSE051306R1\u003c\/strong\u003e Analog Input Module, operates as a dedicated hardware component for multi-channel temperature measurement within ABB System 800xA platforms. Configured for thermocouple signal processing, the unit accepts low-voltage millivolt inputs directly from field-mounted sensor loops. It converts low-level differential thermal signals into digital values via 15-bit resolution analog-to-digital converters for deterministic execution across control platforms.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eAI835A (3BSE051306R1)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eABB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eSweden\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e2.0 kg (Shipping Weight)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003eStandard Module Slot\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-10 deg C to +60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eSystem Module Bus Powered\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eAnalog Input Modules\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Channels\u003c\/td\u003e\n\u003ctd\u003e8 channels (TC inputs)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eThermocouple Types\u003c\/td\u003e\n\u003ctd\u003eB, C, E, J, K, N, R, S, T\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Range\u003c\/td\u003e\n\u003ctd\u003e-30 mV to +75 mV\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eADC Resolution\u003c\/td\u003e\n\u003ctd\u003e15 bits\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eChannel-to-Channel Isolation \u0026amp; Cold Junction Compensation (CJC)\u003c\/h3\u003e\n\u003cp\u003eThe module incorporates dedicated cold junction compensation (CJC) processing across its 8 input channels to maintain accuracy across broad ambient temperature gradients. Differential millivolt measuring circuits (-30 mV to +75 mV) feature channel-to-channel isolation and input filtering to suppress high-frequency common-mode noise and ground loops in industrial environments. Interfacing directly with thermocouple types B, C, E, J, K, N, R, S, and T, internal linearization tables ensure precise digitalization before transmitting values over the control bus.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: How does the AI835A handle cold junction compensation for varying thermocouple sensor types?\u003c\/p\u003e\n\u003cp\u003eA: The AI835A module utilizes built-in cold junction compensation sensors on the reference termination unit alongside software linearization algorithms tailored to thermocouple types B, C, E, J, K, N, R, S, and T.\u003c\/p\u003e\n\u003cp\u003eQ: What resolution does the module provide across its -30 mV to +75 mV measurement range?\u003c\/p\u003e\n\u003cp\u003eA: The internal analog-to-digital converter operates at 15-bit resolution, providing fine voltage step discretization to capture subtle temperature variations across all 8 differential channels.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003eMount the module securely into its designated I\/O terminal block slot, ensuring full engagement of backplane connectors before locking module retention tabs.\u003c\/li\u003e\n\u003cli\u003eConnect thermocouple extension wires using appropriate compensation cabling matching the specific thermocouple type (B, C, E, J, K, N, R, S, or T) used at the sensing point.\u003c\/li\u003e\n\u003cli\u003eTerminate signal cable shields to designated functional ground points on the module baseboard, ensuring single-point grounding to prevent ground loop currents.\u003c\/li\u003e\n\u003cli\u003eRoute thermocouple input wiring away from high-voltage AC power lines and variable frequency drive cables in wire raceways to avoid electromagnetic interference.\u003c\/li\u003e\n\u003c\/ol\u003e","brand":"ABB","offers":[{"title":"Default Title","offer_id":45401617793139,"sku":"AI835A 3BSE051306R1","price":233.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0644\/4348\/2227\/files\/ABBAI835A3BSE051306R1_d55c5986-8956-4ef6-8713-1635021f6876.png?v=1787732879","url":"https:\/\/www.dcssupplier.com\/ar\/products\/abb-ai835a-3bse051306r1-analog-input","provider":"DcsSupplier Limited","version":"1.0","type":"link"}