{"product_id":"ge-fanuc-ic693mdl230c-series-90-30-isolated-ac-input-module","title":"GE Fanuc IC693MDL230C Series 90-30 Isolated AC Input Module","description":"\u003cp\u003eThe \u003cstrong\u003eGE Fanuc IC693MDL230C\u003c\/strong\u003e is an 8-point isolated AC input module designed for the Series 90-30 programmable logic controller (PLC) platform. It accepts 120 VAC field signals from external devices such as pushbuttons, limit switches, and electronic proximity switches. Each input point has an individual status LED, while the module uses a common power input terminal for its eight input circuits.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eElectrical Isolation and Protection\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe module provides 1500 V RMS isolation between the field side and logic side. This electrical separation helps isolate field wiring from the PLC logic circuitry.\u003c\/p\u003e\n\u003cp\u003eThe red edge marking on the module identifies it as a high-voltage I\/O device. Appropriate wiring practices and electrical isolation precautions should be observed when connecting field circuits.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eLED Status Indication\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe front LED block contains eight indicators corresponding to the eight input points. These indicators allow maintenance personnel to identify individual input states during PLC troubleshooting.\u003c\/p\u003e\n\u003cp\u003eThe hinged front door includes a removable identification card for recording circuit descriptions and field device references. This helps technicians associate each input point with its corresponding machine signal.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eInstallation and Compatibility\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe IC693MDL230C is designed for installation in an available I\/O slot on a GE Fanuc Series 90-30 PLC baseplate. Its input connections share a common power input terminal, so the field wiring arrangement should be checked before commissioning.\u003c\/p\u003e\n\u003cp\u003eBefore installation or replacement, verify the module revision, baseplate configuration, AC supply voltage, and field wiring requirements. Do not connect DC field signals to this AC input module.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eTechnical Specifications\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eIC693MDL230C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eGE Fanuc Emerson\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Line\u003c\/td\u003e\n\u003ctd\u003eSeries 90-30\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eIsolated AC Input Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Type\u003c\/td\u003e\n\u003ctd\u003e8-Point AC Input\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Voltage\u003c\/td\u003e\n\u003ctd\u003e120 VAC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Frequency\u003c\/td\u003e\n\u003ctd\u003e50\/60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Inputs\u003c\/td\u003e\n\u003ctd\u003e8\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Current at Rated Voltage\u003c\/td\u003e\n\u003ctd\u003e14.5 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eField-to-Logic Isolation\u003c\/td\u003e\n\u003ctd\u003e1500 V RMS\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Power Type\u003c\/td\u003e\n\u003ctd\u003eAC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDC Input Support\u003c\/td\u003e\n\u003ctd\u003eNo\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Input Configuration\u003c\/td\u003e\n\u003ctd\u003eOne common power input terminal\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Characteristics\u003c\/td\u003e\n\u003ctd\u003eReactive\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLED Indicators\u003c\/td\u003e\n\u003ctd\u003e8\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLED Arrangement\u003c\/td\u003e\n\u003ctd\u003eOne indicator per input point\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLED Colors\u003c\/td\u003e\n\u003ctd\u003eGreen and red (as described in supplied source)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCompatible Platform\u003c\/td\u003e\n\u003ctd\u003eGE Fanuc Series 90-30 PLC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting\u003c\/td\u003e\n\u003ctd\u003eSeries 90-30 PLC baseplate I\/O slot\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e1.50 lbs (0.68 kg)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003e\u003cstrong\u003eFrequently Asked Questions\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Can the IC693MDL230C accept 24 VDC input signals?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: No. The IC693MDL230C is a 120 VAC input module designed for AC field signals. DC input sources are not supported.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: How many field devices can the IC693MDL230C monitor?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: The module provides eight isolated input points, allowing it to monitor up to eight individual field signals, subject to the common power input and field wiring arrangement.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What is the purpose of the 1500 V RMS isolation rating?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: It specifies the electrical isolation between the field side and PLC logic side. This separation helps protect the control-side circuitry from electrical disturbances originating in field circuits.\u003c\/p\u003e","brand":"GE Fanuc","offers":[{"title":"Default Title","offer_id":67285469560947,"sku":"IC693MDL230C","price":88.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0644\/4348\/2227\/files\/IC693MDL930_Cocoai_a76eae1f-f807-4808-ba93-14b45392e2a2.jpg?v=1795422010","url":"https:\/\/www.dcssupplier.com\/ar\/products\/ge-fanuc-ic693mdl230c-series-90-30-isolated-ac-input-module","provider":"DcsSupplier Limited","version":"1.0","type":"link"}