{"product_id":"honeywell-rm7888a1019-7800-series-primary-control-module","title":"Honeywell RM7888A1019 7800 Series Primary Control Module","description":"\u003cp\u003eConfigured for flame safeguard sequencing and valve control in industrial burner automation, the \u003cstrong\u003eHoneywell RM7888A1019\u003c\/strong\u003e (\u003cstrong\u003eRM7888A\u003c\/strong\u003e Primary Control Module) provides direct physical\/electrical execution. Operating on a nominal 120 VAC line supply at 50\/60 Hz, this microprocessor-based relay module coordinates signal processing from remote flame detectors and safety limit loops. The chassis mounts directly to dedicated wiring subbases, interfacing operational status signals with PLC hardware architectures via standardized terminal assignments while managing critical pilot and main fuel valve timing cycles.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eRM7888A1019\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e3 lbs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003ePlug-in form factor for Q7800 subbases\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-40 deg C to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e10 W maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eVoltage Rating\u003c\/td\u003e\n\u003ctd\u003e120 VAC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Voltage Frequency\u003c\/td\u003e\n\u003ctd\u003e50\/60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStorage Temp\u003c\/td\u003e\n\u003ctd\u003e-40 deg C to 66 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHumidity Range\u003c\/td\u003e\n\u003ctd\u003e85% RH (non-condensing)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Total Connected Load\u003c\/td\u003e\n\u003ctd\u003e2000 VA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePilot Type\u003c\/td\u003e\n\u003ctd\u003eSelectable\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting Type\u003c\/td\u003e\n\u003ctd\u003ePlug-in module on Q7800A1005\/Q7800B1003 wiring subbase\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMain Flame Establishing Period\u003c\/td\u003e\n\u003ctd\u003e15 seconds\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePilot Flame Establishing Period\u003c\/td\u003e\n\u003ctd\u003e4 seconds\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eProcess Control \u0026amp; Channel Isolation Protocols\u003c\/h3\u003e\n\u003cp\u003eThe Honeywell RM7888A1019 integrates high-integrity channel-to-channel isolation across its low-voltage sensor inputs and line-voltage output drivers to isolate system noise from external PLC interfaces. Designed to monitor flame signal strength without signal degradation, the unit accepts input from UV, optical, or flame rod sensors while delivering isolated status feedback across local communication buses. Auxiliary output relays maintain galvanic separation between internal logic circuits and 120 VAC fuel safety shut-off valves, ensuring fast response times under flameout conditions.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Can the RM7888A1019 module be hot-swapped into an active Q7800 wiring subbase under load?\u003c\/p\u003e\n\u003cp\u003eA: No. Line voltage (120 VAC) must be de-energized prior to inserting or removing the RM7888A1019 module from the Q7800A1005 or Q7800B1003 wiring subbase to prevent electrical arcing, physical pin damage, or unintended actuation of fuel valves.\u003c\/p\u003e\n\u003cp\u003eQ: What wiring constraints must be observed for the pilot and main flame ignition outputs?\u003c\/p\u003e\n\u003cp\u003eA: Output loads must not exceed the combined total rating of 2000 VA across all energized terminals. Signal lines from flame sensors must run in grounded metallic conduit separate from high-voltage ignition transformer leads to avoid cross-talk and nuisance shutdowns.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003eMount the Q7800A1005 or Q7800B1003 wiring subbase inside an NEMA-rated enclosure using standard mounting hardware in a vertical orientation to maintain adequate convection cooling across the internal 10 W power dissipation circuit.\u003c\/li\u003e\n\u003cli\u003eEnsure all field wiring complies with local electrical codes. Run flame detector leads in separate, grounded steel conduits; maintain minimum 5-thread engagement for all threaded NPT conduit entries to enforce physical strain relief.\u003c\/li\u003e\n\u003cli\u003eInspect keying slot alignment on the subbase before press-fitting the RM7888A1019 module into place. Secure side locking screws to establish low-resistance backplane ground connection before applying 120 VAC main power.\u003c\/li\u003e\n\u003c\/ol\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":45414738624627,"sku":"RM7888A1019","price":88.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0644\/4348\/2227\/files\/RM7898A1000_2_64a1bd29-bf48-4a5c-bbc2-a2cbdec05ab7.png?v=1787898539","url":"https:\/\/www.dcssupplier.com\/ar\/products\/honeywell-rm7888a1019-7800-series-primary-control-module","provider":"DcsSupplier Limited","version":"1.0","type":"link"}