{"product_id":"remote-i-o-interface-modules-schneider-electric-asp890001","title":"Remote I\/O Interface Modules | Schneider Electric ASP890001","description":"\u003cp\u003eThe \u003cstrong\u003eASP890001\u003c\/strong\u003e is a Remote I\/O (RIO) interface module from Schneider Electric's Modicon 800 product line. It provides communication between compatible 984 Programmable Controllers and remote I\/O drops over a high-speed RIO link operating at 1.544 Mbits\/s. The module supports linear and dual redundant RIO topologies and handles up to 1024 input bits and 1024 output bits per drop.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eRIO Communication and Network Topology\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe ASP890001 supports two RIO network configurations: linear and dual redundant. These configurations provide different communication arrangements for connecting remote I\/O drops to the controller system. Dual redundant topology provides an alternative communication path, subject to the configuration of the complete RIO network.\u003c\/p\u003e\n\u003cp\u003eThe communication link operates at 1.544 Mbits\/s. The specified communication link time is less than 1 ms for 256 I\/O points, providing a reference for evaluating data transfer performance in the configured system.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eI\/O Capacity and Drop Configuration\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eEach remote I\/O drop can support up to 1024 input bits and 1024 output bits. This capacity defines the supported digital I\/O data size per drop and should be considered when calculating the total I\/O requirements of the control system.\u003c\/p\u003e\n\u003cp\u003eDIP switches provide RIO drop address configuration. Correct address assignment is necessary to identify each remote drop within the network and avoid addressing conflicts.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eHold-up Time and Diagnostic Indicators\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe module provides a programmable drop hold-up time from 0.3 to 100 seconds, adjustable in 100 ms increments. This setting determines how long the remote I\/O drop maintains its specified hold-up behavior following a communication interruption. The appropriate setting depends on the control system response requirements and the configured recovery strategy.\u003c\/p\u003e\n\u003cp\u003eLED indicators provide status information for the RIO interface and support communication diagnostics during commissioning and maintenance. These indicators help technicians assess module status without relying exclusively on controller-side diagnostic information.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eTechnical Specifications\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eASP890001\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Line\u003c\/td\u003e\n\u003ctd\u003eModicon 800\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eRIO Interface Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSupported Controller Types\u003c\/td\u003e\n\u003ctd\u003e984 Programmable Controllers\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommunication Interface\u003c\/td\u003e\n\u003ctd\u003eRemote I\/O (RIO)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRIO Communication Speed\u003c\/td\u003e\n\u003ctd\u003e1.544 Mbits\/s\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommunication Link Time\u003c\/td\u003e\n\u003ctd\u003eLess than 1 ms for 256 I\/O points\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSupported RIO Topologies\u003c\/td\u003e\n\u003ctd\u003eLinear, Dual Redundant\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRIO Cable Ports\u003c\/td\u003e\n\u003ctd\u003e1 or 2 F connector ports, model dependent\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eI\/O Capacity per Drop\u003c\/td\u003e\n\u003ctd\u003eUp to 1024 input bits and 1024 output bits\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProgrammable Drop Hold-up Time\u003c\/td\u003e\n\u003ctd\u003e0.3-100 seconds\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHold-up Time Adjustment\u003c\/td\u003e\n\u003ctd\u003e100 ms increments\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e1.85 A at +5 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConfiguration Method\u003c\/td\u003e\n\u003ctd\u003eDIP switches\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDiagnostic Indicators\u003c\/td\u003e\n\u003ctd\u003eRIO interface and status LEDs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Slot Size\u003c\/td\u003e\n\u003ctd\u003e1.5 slots in I\/O housing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e1.36 kg (3.00 lbs)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003e\u003cstrong\u003eInstallation and Configuration Considerations\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe ASP890001 occupies 1.5 slots in the I\/O housing. Before replacement or installation, verify the available rack space and confirm that the module matches the existing Modicon 800 system configuration.\u003c\/p\u003e\n\u003cp\u003eThe RIO drop address must be configured using the DIP switches. For redundant network arrangements, confirm the required cable connections and topology against the installed system design. The supplied information identifies F connector ports but does not establish a universal port count for every configuration.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eFrequently Asked Questions\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Which controller systems are compatible with the ASP890001?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: The supplied specifications identify 984 Programmable Controllers as supported controller types. Compatibility with a particular controller configuration should be checked against the system hardware documentation.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Does the ASP890001 support redundant RIO communication?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: Yes. It supports both linear and dual redundant RIO topologies. The availability of redundant communication depends on the configuration and supporting components of the complete RIO network.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: How is the remote I\/O drop address configured?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: The module uses DIP switches to set the RIO drop address. The address must correspond to the assigned position in the system configuration.\u003c\/p\u003e","brand":"Schneider Electric","offers":[{"title":"Default Title","offer_id":67285438398579,"sku":"ASP890001","price":88.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0644\/4348\/2227\/files\/AS-J890-002_Cocoai_4ef04f6b-3275-4bd7-9c09-a15ea5d5a7bb.jpg?v=1795420803","url":"https:\/\/www.dcssupplier.com\/ar\/products\/remote-i-o-interface-modules-schneider-electric-asp890001","provider":"DcsSupplier Limited","version":"1.0","type":"link"}