{"product_id":"schneider-tsxpsy3610mc-power-supply","title":"Schneider TSXPSY3610MC Power Supply","description":"\u003cp\u003eThe \u003cstrong\u003eTSXPSY3610MC\u003c\/strong\u003e is a conformal-coated 24 VDC double-format power supply module designed for the Schneider Electric Modicon Premium automation platform. Operating on a nominal 24 VDC supply voltage (19.2 to 30 VDC), it delivers a total useful secondary power of 50 W to drive backplane electronics and external circuits. Featuring Humiseal 1A33 conformal coating, this variant provides enhanced environmental protection for reliable operation in harsh industrial atmospheres.\u003c\/p\u003e\n\u003ch3\u003ePower Distribution \u0026amp; Output Characteristics\u003c\/h3\u003e\n\u003cp\u003eThe module draws up to 2,700 mA of input current at 24 VDC, managing an activation inrush current of 150 A ($I^2t$ of $20\\text{ A}^2\\text{s}$). It converts the primary supply into two dedicated secondary DC outputs: a 5 VDC rail supplying up to 7 A (35 W) for backplane logic and processing modules, and a 24 VDC relay power supply delivering up to 0.6 A (19 W). Integrated secondary protection safeguards connected systems against short circuits, overvoltages, and current overloads.\u003c\/p\u003e\n\u003ch3\u003eDiagnostics \u0026amp; Environmental Standards\u003c\/h3\u003e\n\u003cp\u003eFront-panel status is monitored via local LED indicators: a green LED displays voltage presence (OK), while a red LED signals a battery fault (BAT). The unit features an IP20 protection rating with TC protective treatment, operating in ambient temperatures from 0 to +60 deg C and altitudes up to 2000 m. Certified to UL 508, CSA C22.2, and Class I Division 2 (Groups A, B, C, D) standards, as well as multiple marine certifications (ABS, BV, DNV, GL, LR, RINA, RMRS), it maintains immunity to microbreaks up to 1 ms.\u003c\/p\u003e\n\u003ch3\u003eTechnical Parameters\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eTSXPSY3610MC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSeries\u003c\/td\u003e\n\u003ctd\u003eModicon Premium\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003ePower Supply Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Format\u003c\/td\u003e\n\u003ctd\u003eDouble\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePrimary Voltage\u003c\/td\u003e\n\u003ctd\u003e24 VDC (19.2 to 30 V)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Current\u003c\/td\u003e\n\u003ctd\u003e2700 mA max at 24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInrush Current\u003c\/td\u003e\n\u003ctd\u003e150 A at 24 VDC ($I^2t$ 20 A²s \/ $It$ 0.5 As)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSecondary Output Voltage 1\u003c\/td\u003e\n\u003ctd\u003e5 VDC (7 A, 35 W)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSecondary Output Voltage 2\u003c\/td\u003e\n\u003ctd\u003e24 VDC Relay Power Supply (0.6 A, 19 W)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTotal Secondary Power\u003c\/td\u003e\n\u003ctd\u003e50 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConformal Coating\u003c\/td\u003e\n\u003ctd\u003eHumiseal 1A33\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtective Treatment\u003c\/td\u003e\n\u003ctd\u003eTC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtection Types\u003c\/td\u003e\n\u003ctd\u003eSecondary overload, overvoltage, short-circuit\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLocal Signalling\u003c\/td\u003e\n\u003ctd\u003e1 Green LED (Voltage presence OK), 1 Red LED (Battery fault BAT)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIP Rating\u003c\/td\u003e\n\u003ctd\u003eIP20\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePollution Degree\u003c\/td\u003e\n\u003ctd\u003e2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e0 to +60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStorage Temperature\u003c\/td\u003e\n\u003ctd\u003e-25 to +70 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Altitude\u003c\/td\u003e\n\u003ctd\u003e0 to 2000 m\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelative Humidity\u003c\/td\u003e\n\u003ctd\u003e10 to 95% non-condensing (Operating) \/ 5 to 95% (Storage)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eImmunity to Microbreaks\u003c\/td\u003e\n\u003ctd\u003e1 ms or less\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDielectric Strength\u003c\/td\u003e\n\u003ctd\u003e2000 V primary\/earth, 2000 V primary\/secondary\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCertifications\u003c\/td\u003e\n\u003ctd\u003eABS, BV, DNV, GL, LR, RINA, RMRS, UL 508, CSA C22.2 No 142 \/ No 213 Class I Div 2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Weight\u003c\/td\u003e\n\u003ctd\u003e0.78 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003eFrequently Asked Questions\u003c\/p\u003e\n\u003cp\u003eQ: What does the \"C\" suffix in TSXPSY3610MC represent? A: The \"C\" suffix indicates that the module features Humiseal 1A33 conformal coating, which protects internal circuitry against humidity and corrosive chemical environments.\u003c\/p\u003e\n\u003cp\u003eQ: What is the maximum load the TSXPSY3610MC can supply on its secondary outputs? A: The module provides a total useful secondary power of 50 W, divided into 35 W (7 A) at 5 VDC for rack electronics and 19 W (0.6 A) at 24 VDC for relay circuits.\u003c\/p\u003e\n\u003cp\u003eQ: Is the TSXPSY3610MC certified for hazardous area and marine installations? A: Yes, it holds Class I Division 2 (Groups A, B, C, D) ratings under CSA C22.2 No 213 and carries marine approvals from ABS, BV, DNV, GL, LR, RINA, and RMRS.\u003c\/p\u003e","brand":"Schneider Electric","offers":[{"title":"Default Title","offer_id":67107438526579,"sku":"TSXPSY3610MC","price":88.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0644\/4348\/2227\/files\/TSXPSY3610M2_Cocoai.jpg?v=1793784392","url":"https:\/\/www.dcssupplier.com\/ar\/products\/schneider-tsxpsy3610mc-power-supply","provider":"DcsSupplier Limited","version":"1.0","type":"link"}