{"product_id":"allen-bradley-1747-l20a-slc-500-fixed-plc-controller","title":"Allen-Bradley 1747-L20A SLC 500 Fixed PLC Controller","description":"\u003cp\u003eThe \u003cstrong\u003e1747-L20A\u003c\/strong\u003e is an Allen-Bradley SLC 500 fixed-style PLC controller with 20 integrated I\/O points, consisting of 12 discrete 120 V AC inputs and 8 AC\/DC relay outputs. It operates from an AC line supply and provides 1K instruction memory, a 4-microsecond bit execution time, and support for optional two-slot expansion racks.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eI\/O Configuration and Electrical Characteristics\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe controller integrates 12 AC input channels and 8 AC\/DC relay output channels. The relay outputs support AC and DC switching, distinguishing this model from fixed controllers equipped with TRIAC outputs.\u003c\/p\u003e\n\u003cp\u003eThe embedded power supply accepts an operating voltage of 85-265 V AC at 47-63 Hz, while the specified line power range is 120-240 V AC. The power supply has a maximum apparent power requirement of 50 VA, a 30 A inrush current rating, and a pre-installed 1.25 A fuse.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eProcessing and Memory\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe 1747-L20A provides 1K instruction capacity, with a typical program scan time of 8 ms per 1K instructions and a bit execution time of 4 microseconds. These specifications help determine whether the controller can accommodate the program size and processing requirements of an existing control application.\u003c\/p\u003e\n\u003cp\u003eThe controller uses capacitor-backed RAM, with optional battery backup available through the compatible 1747-BA battery assembly. The supplied information also identifies EEPROM and UVPROM as program backup options. Capacitor backup is specified for up to 30 days in one description, while battery-backed RAM retention is stated as up to 5 years.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eExpansion and Communication Connections\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe controller supports optional two-slot expansion racks for additional I\/O capacity. Its integrated hardware configuration provides the basic 20 I\/O points without requiring a separate base I\/O module.\u003c\/p\u003e\n\u003cp\u003eThe specified communication cable is Belden 9463, and the connection hardware uses a 6-pin Phoenix connector. These details should be checked when identifying existing cabling and connector arrangements during maintenance or replacement.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eStatus Indication\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eFive front-panel LED indicators provide information about controller operation and fault conditions:\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003ePOWER: Indicates controller power status.\u003c\/li\u003e\n\u003cli\u003ePC RUN: Indicates processor operating status.\u003c\/li\u003e\n\u003cli\u003eCPU FAULT: Indicates a processor fault.\u003c\/li\u003e\n\u003cli\u003eFORCED I\/O: Indicates forced I\/O conditions.\u003c\/li\u003e\n\u003cli\u003eBATTERY LOW: Indicates a low battery condition.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eThe BATTERY LOW indicator is particularly relevant when the optional battery backup is installed, as battery condition affects the retention of RAM contents during power interruptions.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eInstallation and Environmental Conditions\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe 1747-L20A uses panel mounting and supports installation in an enclosure. The supplied specifications identify an operating temperature range of 0-60 deg C and relative humidity of 5-95% non-condensing.\u003c\/p\u003e\n\u003cp\u003eIts stated mechanical resistance includes 30 G operational shock and 2.5 G vibration over a frequency range of 10-500 Hz. These conditions should be considered when checking the suitability of the controller for its installation environment.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eTechnical Specifications\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e1747-L20A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eAllen-Bradley\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Line\u003c\/td\u003e\n\u003ctd\u003eSLC 500\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHardware Type\u003c\/td\u003e\n\u003ctd\u003eSLC 500 Fixed Style Hardware\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Type\u003c\/td\u003e\n\u003ctd\u003eFixed Controller\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTotal I\/O Points\u003c\/td\u003e\n\u003ctd\u003e20\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDiscrete Inputs\u003c\/td\u003e\n\u003ctd\u003e12\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Voltage\u003c\/td\u003e\n\u003ctd\u003e120 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDiscrete Outputs\u003c\/td\u003e\n\u003ctd\u003e8\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Type\u003c\/td\u003e\n\u003ctd\u003eAC\/DC Relay\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLine Power\u003c\/td\u003e\n\u003ctd\u003e120-240 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Supply Operating Voltage\u003c\/td\u003e\n\u003ctd\u003e85-265 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Supply Frequency\u003c\/td\u003e\n\u003ctd\u003e47-63 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Power Requirement\u003c\/td\u003e\n\u003ctd\u003e50 VA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Supply Inrush Current\u003c\/td\u003e\n\u003ctd\u003e30 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIntegral Fuse\u003c\/td\u003e\n\u003ctd\u003e1.25 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eController Memory\u003c\/td\u003e\n\u003ctd\u003e1K instructions\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTypical Program Scan Time\u003c\/td\u003e\n\u003ctd\u003e8 ms per 1K instructions\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBit Execution Time\u003c\/td\u003e\n\u003ctd\u003e4 microseconds\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMemory Type\u003c\/td\u003e\n\u003ctd\u003eCapacitor-backed RAM\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCapacitor Backup Duration\u003c\/td\u003e\n\u003ctd\u003eUp to 30 days\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOptional Battery\u003c\/td\u003e\n\u003ctd\u003e1747-BA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBattery-Backed RAM Retention\u003c\/td\u003e\n\u003ctd\u003eUp to 5 years\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProgram Backup Options\u003c\/td\u003e\n\u003ctd\u003eEEPROM or UVPROM\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Supply Hold-Up Time\u003c\/td\u003e\n\u003ctd\u003e20-700 ms (load-dependent)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHigh-Speed Counter\u003c\/td\u003e\n\u003ctd\u003eNo\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eExpansion Capability\u003c\/td\u003e\n\u003ctd\u003eOptional two-slot expansion racks\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStatus Indicators\u003c\/td\u003e\n\u003ctd\u003ePOWER, PC RUN, CPU FAULT, FORCED I\/O, BATTERY LOW\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommunication Cable\u003c\/td\u003e\n\u003ctd\u003eBelden 9463\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConnector\u003c\/td\u003e\n\u003ctd\u003e6-pin Phoenix connector\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCircuit Wire Size\u003c\/td\u003e\n\u003ctd\u003e24 AWG\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e0 to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelative Humidity\u003c\/td\u003e\n\u003ctd\u003e5-95%, non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperational Shock\u003c\/td\u003e\n\u003ctd\u003e30 G\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eVibration Resistance\u003c\/td\u003e\n\u003ctd\u003e2.5 G at 10-500 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting\u003c\/td\u003e\n\u003ctd\u003ePanel mount\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e3.75 lbs (1.70 kg)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003e\u003cstrong\u003eFrequently Asked Questions\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What is the difference between the 1747-L20A and the 1747-L20B?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: The main documented difference is the output configuration. The 1747-L20A has 8 AC\/DC relay outputs, whereas the 1747-L20B has 8 AC TRIAC outputs. Their input configurations are also specified as 12-channel, 120 V AC inputs. These output types are not interchangeable without checking the field load and wiring requirements.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Does the 1747-L20A support battery-backed memory?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: Yes. The controller supports the optional 1747-BA lithium battery assembly for RAM retention. The supplied specifications state up to 5 years of battery-backed retention, compared with capacitor backup alone.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Can the 1747-L20A be expanded with additional I\/O?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: Yes. The controller supports optional two-slot expansion racks. The exact compatible expansion hardware should be verified against the applicable SLC 500 configuration documentation.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Does the 1747-L20A include a high-speed counter?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: No. The supplied specifications identify this controller as having no high-speed counter. Applications requiring dedicated high-speed pulse counting need a separately verified solution.\u003c\/p\u003e","brand":"Allen-Bradley","offers":[{"title":"Default Title","offer_id":67305954803827,"sku":"1747-L20A","price":88.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0644\/4348\/2227\/files\/1747-L20F2_Cocoai_174eac26-bc07-4f5c-b9fd-f02b70fe4a22.jpg?v=1795596645","url":"https:\/\/www.dcssupplier.com\/products\/allen-bradley-1747-l20a-slc-500-fixed-plc-controller","provider":"DcsSupplier Limited","version":"1.0","type":"link"}