{"product_id":"allen-bradley-1752-l24bbb-smartguard-600-safety-controller","title":"Allen Bradley 1752-L24BBB SmartGuard 600 Safety Controller","description":"\u003cp\u003eThe \u003cstrong\u003eAllen Bradley 1752-L24BBB\u003c\/strong\u003e is a programmable electronic safety controller from the SmartGuard 600 product line. It provides 16 digital inputs, 8 digital outputs, and 4 test pulse sources for monitoring safety devices and controlling safety-related outputs. USB and DeviceNet interfaces support programming and network communication, while EtherNet\/IP connectivity supports CIP Safety and standard CIP communications.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eDigital I\/O Configuration\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe 1752-L24BBB combines sinking-type digital inputs with sourcing-type digital outputs. Its 16 inputs support input circuit diagnostics, configurable on-and-off delays, and dual-channel operation. These functions allow the controller to monitor safety input states and detect discrepancies in supported input circuits.\u003c\/p\u003e\n\u003cp\u003eThe 8 sourcing outputs include output circuit diagnostics, overcurrent detection, and protection. Four test pulse sources provide test signals for compatible input circuits, with overcurrent monitoring and protection. The controller also supports current monitoring for a muting lamp.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eCommunication and Programming\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe controller supports DeviceNet safety communications and EtherNet\/IP connectivity for CIP Safety and standard CIP messaging. Its USB port provides a local programming interface and can also be used to configure network devices.\u003c\/p\u003e\n\u003cp\u003eRSNetWorx provides access to internal controller status information and I\/O data. The available communication interfaces allow the controller to exchange safety and standard control information with compatible network devices.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eTechnical Specifications\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e1752-L24BBB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eAllen Bradley\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Line\u003c\/td\u003e\n\u003ctd\u003eSmartGuard 600\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eProgrammable Electronic Safety Controller\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePart Number\u003c\/td\u003e\n\u003ctd\u003e1752-L24BBB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eUPC\u003c\/td\u003e\n\u003ctd\u003e662074535781\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDigital Inputs\u003c\/td\u003e\n\u003ctd\u003e16\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDigital Outputs\u003c\/td\u003e\n\u003ctd\u003e8\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTest Pulse Sources\u003c\/td\u003e\n\u003ctd\u003e4\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Type\u003c\/td\u003e\n\u003ctd\u003eCurrent Sinking\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Type\u003c\/td\u003e\n\u003ctd\u003eCurrent Sourcing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTest Output Type\u003c\/td\u003e\n\u003ctd\u003eCurrent Sourcing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDeviceNet Voltage Range\u003c\/td\u003e\n\u003ctd\u003e11-25 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCurrent Consumption\u003c\/td\u003e\n\u003ctd\u003e230 mA at 24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Current\u003c\/td\u003e\n\u003ctd\u003e4.5 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOn-State Input Voltage\u003c\/td\u003e\n\u003ctd\u003e11 VDC minimum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOff-State Input Voltage\u003c\/td\u003e\n\u003ctd\u003e5 VDC maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOff-State Input Current\u003c\/td\u003e\n\u003ctd\u003e1 mA maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePulse Test Output Current\u003c\/td\u003e\n\u003ctd\u003e0.7 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePulse Test Output Surge Current\u003c\/td\u003e\n\u003ctd\u003e0.7 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePulse-Test Off-State Voltage\u003c\/td\u003e\n\u003ctd\u003e1.2 V maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePulse-Test Output Leakage Current\u003c\/td\u003e\n\u003ctd\u003e0.1 mA maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Current\u003c\/td\u003e\n\u003ctd\u003e0.5 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Surge Current\u003c\/td\u003e\n\u003ctd\u003e0.5 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOff-State Output Voltage\u003c\/td\u003e\n\u003ctd\u003e1.2 V maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOff-State Output Leakage Current\u003c\/td\u003e\n\u003ctd\u003e0.1 mA maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eI\/O Terminal Screw Torque\u003c\/td\u003e\n\u003ctd\u003e0.56-0.79 N-m\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e1.38 lb (0.62 kg)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003e\u003cstrong\u003eFrequently Asked Questions\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: How many digital I\/O points does the 1752-L24BBB provide?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: The controller provides 16 digital inputs and 8 digital outputs, together with 4 test pulse sources. The inputs use a current-sinking configuration, while the outputs and test pulse sources use current-sourcing configurations.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Which communication interfaces are available on the 1752-L24BBB?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: The controller supports USB, DeviceNet, and EtherNet\/IP connectivity. DeviceNet supports safety communications, while EtherNet\/IP supports CIP Safety and standard CIP communications. USB is used for local programming and network device configuration.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What configuration protection features does this SmartGuard 600 controller provide?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: The 1752-L24BBB uses SNN verification, a configuration signature, configuration and safety locks, and password protection. These features help protect the safety configuration and verify its identity during system commissioning and maintenance.\u003c\/p\u003e","brand":"Allen-Bradley","offers":[{"title":"Default Title","offer_id":67236053614707,"sku":"1752-L24BBB","price":88.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0644\/4348\/2227\/files\/1752-L24BBB2_Cocoai.jpg?v=1794896761","url":"https:\/\/www.dcssupplier.com\/products\/allen-bradley-1752-l24bbb-smartguard-600-safety-controller","provider":"DcsSupplier Limited","version":"1.0","type":"link"}