{"product_id":"emerson-epro-con021-pr6424-002-130-eddy-current-monitoring-system","title":"Emerson EPRO CON021+PR6424\/002-130 Eddy Current Monitoring System","description":"\u003cp\u003eThe \u003cstrong\u003eEmerson EPRO CON021+PR6424\/002-130\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003eCON021+PR6424\u003c\/strong\u003e Eddy Current Monitoring System, operates as a dedicated hardware component for non-contact shaft displacement and vibration measurement within EPRO machine condition monitoring networks. This 16 mm probe assembly translates rotor dynamics into standardized voltage curves, tracking axial position and radial displacement across high-speed industrial turbomachinery.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eCON021+PR6424\/002-130\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eEmerson (EPRO)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eGermany\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e~200 g (7.05 oz)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e16 mm probe diameter; Standard DIN converter module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-35 to 150 deg C (-31 to 302 deg F)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eSized by loop interface (Typically -23 V to -32 VDC)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eProximity Sensors\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMeasurement Range\u003c\/td\u003e\n\u003ctd\u003eStatic: +\/- 2.0 mm; Dynamic: 0 to 1000 um\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSensitivity\u003c\/td\u003e\n\u003ctd\u003e4 V\/mm (101.6 mV\/mil) +\/- 5%\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLinearity Deviation\u003c\/td\u003e\n\u003ctd\u003e\u0026lt;= +\/- 1.5%\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eShaft Diameter Requirement\u003c\/td\u003e\n\u003ctd\u003e\u0026gt;= 80 mm target minimum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eMechanical Monitoring and TSI Features\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eEddy-Current Probe Scaling:\u003c\/strong\u003e The PR6424 series utilizes high-frequency electromagnetic induction to measure the distance between the sensor tip and the ferromagnetic shaft. The system is factory-calibrated to a sensitivity of 4 V\/mm, with linearity maintained at \u0026lt;= +\/- 1.5% through consistent target material interaction.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eGap Voltage Validation:\u003c\/strong\u003e Operation requires an initial nominal air gap of approximately 2.7 mm. Precise adjustment of this gap is mandatory to ensure the output signal remains within the linear region of the CON021 converter range (typically -4 V to -20 VDC).\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eRotor Dynamics and Signal Processing:\u003c\/strong\u003e The assembly supports shaft surface speeds up to 2,500 m\/s, capturing dynamic vibration frequencies relevant for diagnosing rotor imbalance, oil whirl, or shaft centerline migration. The temperature coefficient (\u0026lt; 4% \/ 100 K) adheres to API 670 machinery protection standards, ensuring minimal measurement drift during thermal expansion of the turbine casing.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Can the 130 mm probe lead be extended in the field?\u003c\/p\u003e\n\u003cp\u003eA: No. The lead length of 130 mm is fixed at the factory. Any modification, splicing, or unauthorized extension of the coaxial cable will alter the total capacitance of the loop, effectively invalidating the system calibration and causing significant measurement errors in vibration amplitude.\u003c\/p\u003e\n\u003cp\u003eQ: What is the risk of using a target shaft smaller than 80 mm?\u003c\/p\u003e\n\u003cp\u003eA: Using a shaft diameter below 80 mm causes flux leakage, where electromagnetic field lines wrap around the shaft curvature rather than concentrating on the sensing area. This results in reduced sensitivity, signal non-linearity, and a significant deviation from the nominal 4 V\/mm scaling.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eMounting and Air Gap Adjustment:\u003c\/strong\u003e Thread the 16 mm probe body into the machine casing mount. Using a non-magnetic feeler gauge, establish the nominal 2.7 mm air gap between the probe tip and the target surface. Once set, torque the locknuts against the mounting flange to ensure the probe remains stationary during transient vibrations.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSignal Path Grounding:\u003c\/strong\u003e The coaxial signal path must remain ungrounded at the sensor end to prevent ground loops. Route the signal cable through metallic, grounded conduit to protect against electromagnetic interference (EMI) from high-power field cabling. The cable shield must be terminated strictly at the CON021 converter module ground point inside the instrumentation cabinet.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Emerson Epro","offers":[{"title":"Default Title","offer_id":45147362099315,"sku":"CON021+PR6424\/002-130","price":88.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0644\/4348\/2227\/files\/screenshot_2026-06-01_15-55-08_e6b7ccd5-4ca6-4762-b76c-66235cd258fa.png?v=1782986673","url":"https:\/\/www.dcssupplier.com\/products\/emerson-epro-con021-pr6424-002-130-eddy-current-monitoring-system","provider":"DcsSupplier Limited","version":"1.0","type":"link"}