{"product_id":"ge-fanuc-emerson-ic693mdl645b-series-90-30-discrete-input-module","title":"GE Fanuc Emerson IC693MDL645B Series 90-30 Discrete Input Module","description":"\u003cp\u003eThe \u003cstrong\u003eGE Fanuc Emerson IC693MDL645B\u003c\/strong\u003e is a 16-point DC discrete input module for the Series 90-30 PLC platform. It supports positive and negative logic input configurations, accepting 24 VDC nominal field signals from devices such as pushbuttons, limit switches, proximity switches, and auxiliary contacts. The module provides individual channel status LEDs, field-to-logic isolation, and a single common input group.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eFunctional Description\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe IC693MDL645B interfaces external DC switching devices with the Series 90-30 PLC. It provides 16 input channels arranged in one group with a single common terminal. Both positive and negative logic configurations are supported, allowing the module to accommodate different field wiring arrangements.\u003c\/p\u003e\n\u003cp\u003eWhen an input receives sufficient current, the corresponding channel is registered as logic 1 in the PLC input status table (%I). This allows the CPU to read the operating states of connected field devices and use them in the control program.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eInput Characteristics and Signal Processing\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe module accepts external signals within a 0-30 VDC range, with a nominal input voltage of 24 VDC. Its ON-state voltage range is 11.5-30 VDC, while voltages between 0 and 5 VDC represent the OFF state. The typical input current is 7 mA at rated voltage.\u003c\/p\u003e\n\u003cp\u003eField-side and logic-side circuits are isolated at 1500 V. This electrical isolation separates the external input wiring from the PLC logic circuitry. The typical ON and OFF response times are both 7 ms, which defines the time required for an input state change to be recognized by the module.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eChannel Monitoring and Wiring\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eSixteen individual LED indicators display the ON\/OFF status of the input channels. The indicators are arranged in two rows, labeled A1-A8 and B1-B8, corresponding to the 16 input points. They provide a local indication of input signal status during commissioning and troubleshooting.\u003c\/p\u003e\n\u003cp\u003eThe module uses a 20-screw removable terminal block supplied with the module. Its wiring arrangement includes the input terminals and a common connection, with additional terminals identified for the isolated 24 VDC output and 0 VDC output. Field devices can use an external power supply or the module's isolated 24 VDC supply, subject to the available supply capacity.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003ePLC Installation and Power Requirements\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe IC693MDL645B occupies one I\/O slot in a Series 90-30 PLC system and is specified for use with 5-slot or 10-slot baseplates. It draws 80 mA from the 5 VDC backplane bus when all inputs are ON, together with 125 mA from the isolated 24 VDC backplane bus or a user-supplied power source.\u003c\/p\u003e\n\u003cp\u003eThese two current requirements should be considered separately when checking PLC power supply capacity. The 5 VDC requirement relates to the module's backplane logic supply, while the isolated 24 VDC supply supports the field-side input circuitry.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eTechnical Specifications\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eIC693MDL645B\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eGE Fanuc Emerson\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Line\u003c\/td\u003e\n\u003ctd\u003eSeries 90-30\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Type\u003c\/td\u003e\n\u003ctd\u003ePositive \/ Negative Discrete Input\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Type\u003c\/td\u003e\n\u003ctd\u003eDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Points\u003c\/td\u003e\n\u003ctd\u003e16\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Configuration\u003c\/td\u003e\n\u003ctd\u003e1 group, single common\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNominal Input Voltage\u003c\/td\u003e\n\u003ctd\u003e24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Voltage Range\u003c\/td\u003e\n\u003ctd\u003e0-30 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Current\u003c\/td\u003e\n\u003ctd\u003e7 mA typical at rated voltage\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eON-State Voltage\u003c\/td\u003e\n\u003ctd\u003e11.5-30 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOFF-State Voltage\u003c\/td\u003e\n\u003ctd\u003e0-5 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eON-State Current\u003c\/td\u003e\n\u003ctd\u003e3.2 mA minimum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOFF-State Current\u003c\/td\u003e\n\u003ctd\u003e1.1 mA maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eField-to-Logic Isolation\u003c\/td\u003e\n\u003ctd\u003e1500 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eON Response Time\u003c\/td\u003e\n\u003ctd\u003e7 ms typical\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOFF Response Time\u003c\/td\u003e\n\u003ctd\u003e7 ms typical\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInternal Power Used\u003c\/td\u003e\n\u003ctd\u003e80 mA at 5 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolated 24 VDC Current\u003c\/td\u003e\n\u003ctd\u003e125 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Type\u003c\/td\u003e\n\u003ctd\u003eDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Width\u003c\/td\u003e\n\u003ctd\u003e1 slot\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLED Indicators\u003c\/td\u003e\n\u003ctd\u003e16, one per channel\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConnector Type\u003c\/td\u003e\n\u003ctd\u003e20-screw removable terminal block\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTerminal Block\u003c\/td\u003e\n\u003ctd\u003eIncluded with module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCompatible Baseplate\u003c\/td\u003e\n\u003ctd\u003eSeries 90-30 5-slot or 10-slot baseplate\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e1.44 lbs (0.65 kg)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLifecycle Status\u003c\/td\u003e\n\u003ctd\u003eDiscontinued \/ Obsolete (as stated in supplied product information)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003e\u003cstrong\u003eFrequently Asked Questions\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: How many input devices can the IC693MDL645B monitor?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: The module supports 16 independent input points in one group with a single common terminal. Each channel has an individual LED indicator for monitoring its input state.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Can the IC693MDL645B accept both positive and negative logic signals?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: Yes. The module supports both positive and negative logic configurations. Field wiring polarity must be arranged according to the applicable wiring diagram and the selected logic configuration.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What should be checked when replacing an IC693MDL645B?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: Verify the complete part number, input voltage requirements, terminal assignments, single-common input configuration, and Series 90-30 baseplate compatibility. Also check the available 5 VDC and isolated 24 VDC power capacity before installing the replacement.\u003c\/p\u003e","brand":"GE Fanuc","offers":[{"title":"Default Title","offer_id":67314251858035,"sku":"IC693MDL645B","price":88.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0644\/4348\/2227\/files\/IC693ALG442B2_Cocoai_84bf60ac-533c-4d6c-bd5b-a49cebf08820.jpg?v=1795662470","url":"https:\/\/www.dcssupplier.com\/products\/ge-fanuc-emerson-ic693mdl645b-series-90-30-discrete-input-module","provider":"DcsSupplier Limited","version":"1.0","type":"link"}