{"product_id":"ge-fanuc-ic660bba020-genius-i-o-analog-block","title":"GE Fanuc IC660BBA020 Genius I\/O Analog Block","description":"\u003cp\u003eThe \u003cstrong\u003eIC660BBA020\u003c\/strong\u003e is a standalone, 24\/48 VDC powered analog I\/O block belonging to the GE Fanuc Genius I\/O system. It features four independent analog input circuits and two independent analog output circuits, providing localized signal conversion and direct Genius Bus communication to host controllers without requiring a local CPU rack.\u003c\/p\u003e\n\u003ch3\u003eSignal Processing and Diagnostic Functionality\u003c\/h3\u003e\n\u003cp\u003eEach channel on the \u003cstrong\u003eIC660BBA020\u003c\/strong\u003e supports software-configurable signal ranges, including 0–10 VDC, ±10 VDC, ±5 VDC, 0–5 VDC, and 4–20 mA (or 1–5 VDC). Analog signals are processed using 12-bit plus sign resolution with a 4 ms update frequency across all points.\u003c\/p\u003e\n\u003cp\u003eThe block incorporates advanced diagnostics. Inputs monitor for underrange, overrange, open wire, and high\/low alarms, while outputs provide underrange and overrange detection. An adjustable input filter ranging from none up to 1024 ms can be set independently per channel to smooth out noisy process signals.\u003c\/p\u003e\n\u003ch3\u003eHardware Architecture and Field Connections\u003c\/h3\u003e\n\u003cp\u003eThe complete \u003cstrong\u003eIC660BBA020\u003c\/strong\u003e block assembly consists of two separable parts: an electronic assembly (\u003cstrong\u003eIC660EBA020\u003c\/strong\u003e) containing the processing board, and a terminal assembly (\u003cstrong\u003eIC660TSA020\u003c\/strong\u003e) housing field wiring terminals and configuration memory. This modular design permits the electronics assembly to be unplugged and serviced without disconnecting field wiring or losing stored configuration settings.\u003c\/p\u003e\n\u003cp\u003ePower to the unit is supplied via Terminals 6 and 7 within an operating voltage window of 18 to 56 VDC. The unit can be monitored or configured locally using a handheld monitor such as the IC66*HHM500 connected to the serial bus terminals.\u003c\/p\u003e\n\u003ch3\u003eTechnical Parameters\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eIC660BBA020\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eGE Fanuc \/ General Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eGenius I\/O Analog Combination Blocks\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Channels\u003c\/td\u003e\n\u003ctd\u003e4 independent analog inputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Channels\u003c\/td\u003e\n\u003ctd\u003e2 independent analog outputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSignal Ranges\u003c\/td\u003e\n\u003ctd\u003e0 to 10 VDC, ±10 VDC, ±5 VDC, 0 to 5 VDC, 4 to 20 mA (1 to 5 VDC)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNominal Power Supply\u003c\/td\u003e\n\u003ctd\u003e24\/48 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Voltage Range\u003c\/td\u003e\n\u003ctd\u003e18 to 56 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Dissipation\u003c\/td\u003e\n\u003ctd\u003e8 W maximum (6 W typical heat dissipation)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eResolution\u003c\/td\u003e\n\u003ctd\u003e12-bit + sign\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eUpdate Frequency\u003c\/td\u003e\n\u003ctd\u003eEvery 4 ms (all channels)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAbsolute Accuracy\u003c\/td\u003e\n\u003ctd\u003e±0.2% of full scale typical at 25 deg C (±0.5% max)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBlock Isolation\u003c\/td\u003e\n\u003ctd\u003e1500 VAC block-to-block isolation\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Filter Selection\u003c\/td\u003e\n\u003ctd\u003eNone, 8, 16, 32, 64, 128, 256, 512, 1024 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Load Impedance\u003c\/td\u003e\n\u003ctd\u003eVoltage mode: ≥ 2000 Ω; Current mode: 0 to 300 Ω\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e0 to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e2.95 lbs (approx. 1.34 kg)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eIC660BBA020\u003c\/strong\u003e is an open-type industrial device that must be mounted inside a protective, clean enclosure free from conductive contaminants. Bus lines must be landed on Terminals 1 through 4 using recommended shielded twisted-pair cabling. DC power connections must be attached to Terminal 6 (DC+) and Terminal 7 (DC-). Ground connections should be properly wired to designated ground terminals (Terminals 5, 12, 20, and 28) to ensure proper shielding and 1500 V block-to-block isolation.\u003c\/p\u003e\n\u003cp\u003eFrequently Asked Questions\u003c\/p\u003e\n\u003cp\u003eQ: What is the main structural difference between the IC660BBA020 and its internal components? A: The complete IC660BBA020 unit consists of the IC660EBA020 electronics assembly and the IC660TSA020 terminal assembly. The terminal assembly remains wired to field devices while the electronics module can be detached for service.\u003c\/p\u003e\n\u003cp\u003eQ: Can the input and output channels be configured for different signal types on the same block? A: Yes, each input and output circuit can be independently software-configured for specific voltage ranges (0–10 V, ±10 V, ±5 V, 0–5 V) or current signals (4–20 mA).\u003c\/p\u003e","brand":"General Electric","offers":[{"title":"Default Title","offer_id":67114668654707,"sku":"IC660BBA020","price":88.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0644\/4348\/2227\/files\/IC660BBA1052_Cocoai_47646240-fa45-4b25-b7fd-9ed97b4bdd5e.jpg?v=1793871861","url":"https:\/\/www.dcssupplier.com\/products\/ge-fanuc-ic660bba020-genius-i-o-analog-block","provider":"DcsSupplier Limited","version":"1.0","type":"link"}