{"product_id":"ge-fanuc-ic693alg390g-analog-output-module","title":"GE Fanuc IC693ALG390G Analog Output Module","description":"\u003cp\u003eConfigured for multi-channel analog signal synthesis in Series 90-30 PLC platforms, the \u003cstrong\u003eGE Fanuc IC693ALG390G\u003c\/strong\u003e (\u003cstrong\u003eIC693ALG390\u003c\/strong\u003e Analog Output Module) provides direct physical\/electrical execution. The module converts 12-bit digital words from the backplane into 2 isolated voltage or current loop signals (0 to +10 V, -10 to +10 V, 4 to 20 mA, or 0 to 20 mA) to control field actuators and control valves.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eIC693ALG390G\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eGE Fanuc\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.85 lbs (0.39 kg)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003eStandard Series 90-30 Single-Slot Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 to 60 deg C (32 to 140 deg F)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e32 mA @ 5 VDC (Backplane), 120 mA @ 24 VDC (User Power)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Channels\u003c\/td\u003e\n\u003ctd\u003e2 Isolated Analog Channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Ranges\u003c\/td\u003e\n\u003ctd\u003e0 to +10 V, -10 to +10 V, 4 to 20 mA, 0 to 20 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eResolution\u003c\/td\u003e\n\u003ctd\u003e12-Bit Digital-to-Analog Converter (DAC)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem Category\u003c\/td\u003e\n\u003ctd\u003ePLCs\/Machine Control\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSub-Category\u003c\/td\u003e\n\u003ctd\u003eAnalog Output Modules\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eBackplane Bus Communication Velocity \u0026amp; I\/O Density Scaling\u003c\/h3\u003e\n\u003cp\u003eInterfacing directly with the Series 90-30 backplane, the IC693ALG390G maintains high backplane bus communication velocity by updating both output channels during each CPU sweep cycle. Internal optocouplers isolate backplane logic circuits from field-side user power supplies and current loops, preventing electrical noise propagation. High-density output conditioning circuits ensure rapid digital-to-analog converter response without introducing sweep lag into execution loops.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: What power sources are required to operate the IC693ALG390G analog output loops?\u003c\/p\u003e\n\u003cp\u003eA: Logic circuits draw 32 mA from the 5 VDC backplane bus, while output current loops require an external 24 VDC user supply providing up to 120 mA.\u003c\/p\u003e\n\u003cp\u003eQ: How are current and voltage ranges selected on the IC693ALG390G module?\u003c\/p\u003e\n\u003cp\u003eA: Output signal formats (0 to +10 V, -10 to +10 V, 4 to 20 mA, or 0 to 20 mA) are defined in CPU system configuration software and through field connector wiring pinouts.\u003c\/p\u003e\n\u003cp\u003eQ: Can the IC693ALG390G module be inserted into the baseplate while power is applied?\u003c\/p\u003e\n\u003cp\u003eA: No. System power to the Series 90-30 baseplate must be completely disconnected before module insertion or removal to prevent electrical damage and backplane errors.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003eDisconnect and lock out all power sources feeding the Series 90-30 rack and field devices before installing the module.\u003c\/li\u003e\n\u003cli\u003eHook the top rear notch of the module casing onto the top rail of the designated baseplate slot.\u003c\/li\u003e\n\u003cli\u003ePivot the module downward until the rear bus connector fully locks into the backplane socket.\u003c\/li\u003e\n\u003cli\u003eConnect field actuators using shielded twisted-pair cabling, grounding the shield braid at one end to prevent ground loops.\u003c\/li\u003e\n\u003cli\u003eTighten the removable terminal block securing screws and route signal wiring away from high-voltage AC conductors.\u003c\/li\u003e\n\u003c\/ol\u003e","brand":"GE","offers":[{"title":"Default Title","offer_id":66750112923763,"sku":"IC693ALG390G","price":88.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0644\/4348\/2227\/files\/IC693MDL753H2_Cocoai.jpg?v=1790750120","url":"https:\/\/www.dcssupplier.com\/products\/ge-fanuc-ic693alg390g-analog-output-module","provider":"DcsSupplier Limited","version":"1.0","type":"link"}