{"product_id":"ge-fanuc-ic697mdl653d-digital-i-o-cards","title":"GE Fanuc IC697MDL653D Digital I\/O Cards","description":"\u003cp\u003eThe \u003cstrong\u003eGE Fanuc IC697MDL653D\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003eIC697MDL653\u003c\/strong\u003e Discrete Input Module, operates as a dedicated hardware component for converting field discrete signals into logic state data within Series 90-70 PLC platforms. Equipped with 32 input points arranged in four isolated groups of eight channels, the card accepts 24 VDC positive or negative logic field inputs across a -3 to +30 VDC signal range. The module transfers field switch status data directly to the host central processing unit via the VME-compliant backplane interface.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eIC697MDL653D\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eGE Fanuc\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e2.13 lbs (0.96 kg)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003eStandard Series 90-70 Module Footprint\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e300 mA at 5 VDC (0.3 A backplane current draw)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Inputs\u003c\/td\u003e\n\u003ctd\u003e32 discrete channels (4 isolated groups of 8)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNominal Input Voltage\u003c\/td\u003e\n\u003ctd\u003e24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Voltage Range\u003c\/td\u003e\n\u003ctd\u003e-3 to +30 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOn-State Voltage \/ Current\u003c\/td\u003e\n\u003ctd\u003e13.5 to 30 VDC \/ 6 mA to 15 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOff-State Voltage \/ Current\u003c\/td\u003e\n\u003ctd\u003e0 to 5 VDC \/ 0 to 2 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNominal Input Current\u003c\/td\u003e\n\u003ctd\u003e10 mA per channel at 24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTypical Input Impedance\u003c\/td\u003e\n\u003ctd\u003e2.6 kOhm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWiring Configuration\u003c\/td\u003e\n\u003ctd\u003ePositive or negative logic (sinking\/sourcing per group)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Filter Response Time\u003c\/td\u003e\n\u003ctd\u003e1 ms or 10 ms (software configurable)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation Rating\u003c\/td\u003e\n\u003ctd\u003e1500 VAC channel-to-backplane; 500 VDC group-to-group\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBackplane Compatibility\u003c\/td\u003e\n\u003ctd\u003eVME standard C.1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eBackplane Bus Communication Velocity \u0026amp; Network Integration\u003c\/h3\u003e\n\u003cp\u003eThe IC697MDL653D maintains backplane bus communication velocity by executing local signal conditioning and configurable digital filtering (1 ms or 10 ms delay options) directly on the module prior to updating the backplane memory map. Local processing reduces host CPU overhead during high-frequency signal changes. Galvanic isolation rated at 1500 VAC protects internal logic tracks against high-voltage field transients, preventing signal noise from corrupting data transfers. Integrated diagnostic LEDs display channel logic states in real time, while software-based configuration eliminates manual DIP switches or jumpers, ensuring firmware flash compatibility across Series 90-70 system racks.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: How is positive or negative (sinking\/sourcing) logic configured for input field wiring?\u003c\/p\u003e\n\u003cp\u003eA: Wiring logic is determined at the group level by the connection made to each group's dedicated common terminal. Connecting the positive voltage supply to the common configures the group for negative logic, while connecting ground to the common configures it for positive logic.\u003c\/p\u003e\n\u003cp\u003eQ: What are the isolation barriers between field input circuits and internal PLC logic?\u003c\/p\u003e\n\u003cp\u003eA: The module provides 1500 VAC isolation between field inputs and the backplane logic bus, as well as 500 VDC isolation between each of the four 8-channel input groups.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003eTurn off main system power before installing or removing the input module from the backplane.\u003c\/li\u003e\n\u003cli\u003eAlign the module card edges with the slot guide channels of the Series 90-70 rack and push firmly until rear backplane connectors seat completely.\u003c\/li\u003e\n\u003cli\u003eTighten top and bottom module panel screws to secure the physical ground path and ensure mechanical stability under vibration.\u003c\/li\u003e\n\u003cli\u003eWire field input devices to the removable terminal block using dedicated common conductors for each 8-channel group according to the chosen sinking or sourcing logic layout.\u003c\/li\u003e\n\u003cli\u003eKeep DC input field wiring physically separated from high-voltage AC motor lines inside wire ducts to avoid electrical noise coupling.\u003c\/li\u003e\n\u003c\/ol\u003e","brand":"GE","offers":[{"title":"Default Title","offer_id":45431120560243,"sku":"IC697MDL653D","price":88.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0644\/4348\/2227\/files\/IC697MDL250F_1200x1200_8c250eb9-79cf-41bb-a78f-3414903dc7c5.jpg?v=1788227931","url":"https:\/\/www.dcssupplier.com\/products\/ge-fanuc-ic697mdl653d-digital-i-o-cards","provider":"DcsSupplier Limited","version":"1.0","type":"link"}