{"product_id":"ge-is200staoh2aaa-analog-output-terminal-board","title":"GE IS200STAOH2AAA Analog Output Terminal Board","description":"\u003cp\u003eConfigured for multi-channel loop actuation and field element positioning in Mark VIe control systems, the \u003cstrong\u003eGE IS200STAOH2AAA\u003c\/strong\u003e (\u003cstrong\u003eIS200STAOH2AAA\u003c\/strong\u003e Analog Output Terminal Board) provides direct physical\/electrical execution. Paired with the IS230SNAOH2A I\/O pack, the assembly converts digital control commands into precise 4-20 mA current or 0-10 V \/ +\/-10 V voltage outputs to adjust control valves, variable speed drives, and process actuators in power and process automation networks.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eIS200STAOH2AAA \/ IS230SNAOH2A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eGE\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.56 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e16.7 cm x 14.8 cm x 5.5 cm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-40 to +85 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eMax 7.0 W (28 VDC nominal supply)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Channels\u003c\/td\u003e\n\u003ctd\u003e4 to 8 channels (configurable)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Signal Types\u003c\/td\u003e\n\u003ctd\u003eCurrent (4-20 mA), Voltage (0-10 V, +\/-10 V)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eD\/A Resolution\u003c\/td\u003e\n\u003ctd\u003e16-bit resolution\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Accuracy\u003c\/td\u003e\n\u003ctd\u003e+\/-0.05% of full scale\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIngress Protection\u003c\/td\u003e\n\u003ctd\u003eIP65 rating\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem Platform\u003c\/td\u003e\n\u003ctd\u003eMark VIe Control Platform\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eBackplane Bus Communication \u0026amp; I\/O Density Scaling\u003c\/h3\u003e\n\u003cp\u003eThe terminal board interacts with the IS230SNAOH2A I\/O pack via high-density terminal headers, receiving real-time data packets over dual deterministic Ethernet interfaces linked to the controller backplane. Onboard 16-bit D\/A conversion circuits deliver signal scaling across all output channels while maintaining fast backplane update rates. The architecture supports both simplex and redundant backplane configurations, allowing automatic channel failover without disrupting loop current continuity or loop execution velocity.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: How do the terminal board and I\/O pack work together during hardware installation?\u003c\/p\u003e\n\u003cp\u003eA: The IS200STAOH2AAA serves as the physical terminal board where field wires land, while the IS230SNAOH2A I\/O pack plugs directly onto the board header connectors to perform signal processing, D\/A conversion, and network communication with the Mark VIe controller.\u003c\/p\u003e\n\u003cp\u003eQ: Can channels be individually configured for either voltage or current loop outputs?\u003c\/p\u003e\n\u003cp\u003eA: Yes, each output channel can be configured independently via system software to drive standard 4-20 mA current loops or voltage signals ranging from 0-10 V to +\/-10 V depending on the connected field device requirements.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eMount the assembly onto standard DIN rails or mounting panels, ensuring proper engagement of the retention clips.\u003c\/li\u003e\n\u003cli\u003eConnect field signal wiring to the terminal block screws, routing 4-20 mA current and voltage signal cables in separate shielded conduits away from high-voltage AC lines.\u003c\/li\u003e\n\u003cli\u003eEnsure all cable shield drain wires terminate at a single chassis ground lug on the enclosure backplate to mitigate high-frequency electrical noise.\u003c\/li\u003e\n\u003cli\u003eVerify 28 VDC nominal power supply rails stay within operating limits before commissioning the connected I\/O pack.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"General Electric","offers":[{"title":"Default Title","offer_id":45371418771571,"sku":"IS200STAOH2AAA","price":88.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0644\/4348\/2227\/files\/screenshot_2026-08-18_16-53-33_1200x1200_a8e6c011-2493-496f-9044-7ea13fe3baf5.jpg?v=1787043951","url":"https:\/\/www.dcssupplier.com\/products\/ge-is200staoh2aaa-analog-output-terminal-board","provider":"DcsSupplier Limited","version":"1.0","type":"link"}