{"product_id":"honeywell-fs-tsro-0824-digital-output-field-termination-assembly","title":"Honeywell FS-TSRO-0824 Digital Output Field Termination Assembly","description":"\u003cp\u003eThe \u003cstrong\u003eFS-TSRO-0824\u003c\/strong\u003e is an advanced digital output field termination assembly engineered by Honeywell for critical industrial safety and control applications. This 8-channel relay termination unit handles high-capacity switching loads up to 250 Vac\/Vdc while delivering robust safety classification up to AK1-6, bridging controller logic directly to demanding field devices.\u003c\/p\u003e\n\u003ch3\u003eElectrical and Switching Performance\u003c\/h3\u003e\n\u003cp\u003eDesigned to operate with a nominal input voltage of 24 Vdc and a maximum input voltage of 36 Vdc, the module features a relay pick-up voltage threshold of 19.2 Vdc. It supports a typical input current of 40 mA at 24 Vdc, driving eight fused output channels rated for a maximum current of 5 A and a minimum output current of 1 mA at 5 V.\u003c\/p\u003e\n\u003ch3\u003eLoad Capacity and Safety Compliance\u003c\/h3\u003e\n\u003cp\u003eThe assembly accommodates a maximum switched load of 1250 VA or 150 W across its output channels, making it suitable for heavy-duty operational requirements. Built to meet stringent industrial safety standards, it achieves a safety class rating of AK1-6 and carries CE, UL, and TÜV approvals pending configurations.\u003c\/p\u003e\n\u003ch3\u003eMechanical Dimensions and Physical Build\u003c\/h3\u003e\n\u003cp\u003eWith physical dimensions measuring 300 x 70 x 60 mm in length, width, and height, this termination assembly is tailored for efficient cabinet layout. It features a shipping weight of 2 kg, balancing robust construction with manageable panel installation requirements.\u003c\/p\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eFS-TSRO-0824\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eDigital Output Field Termination Assembly\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Output Channels\u003c\/td\u003e\n\u003ctd\u003e8\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNominal Input Voltage\u003c\/td\u003e\n\u003ctd\u003e24 Vdc\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMax. Input Voltage\u003c\/td\u003e\n\u003ctd\u003e36 Vdc\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelay Pick-up Voltage\u003c\/td\u003e\n\u003ctd\u003e19.2 Vdc\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Current\u003c\/td\u003e\n\u003ctd\u003eTypically 40 mA at 24 Vdc\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMax. Output Current\u003c\/td\u003e\n\u003ctd\u003e5 A (fused)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMin. Output Current\u003c\/td\u003e\n\u003ctd\u003e1 mA at 5 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMax. Output Voltage\u003c\/td\u003e\n\u003ctd\u003e250 Vac \/ 250 Vdc\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMax. Switched Load\u003c\/td\u003e\n\u003ctd\u003e1250 VA \/ 150 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSafety Class\u003c\/td\u003e\n\u003ctd\u003eAK1-6\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eApprovals\u003c\/td\u003e\n\u003ctd\u003eCE, UL, TÜV approvals pending\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions (L x W x H)\u003c\/td\u003e\n\u003ctd\u003e300 x 70 x 60 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eShipping Weight\u003c\/td\u003e\n\u003ctd\u003e2 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003eFrequently Asked Questions\u003c\/p\u003e\n\u003cp\u003eQ: What is the maximum switched load supported by the FS-TSRO-0824 module? A: The module supports a maximum switched load of 1250 VA or 150 W, with output channels rated up to 250 Vac \/ 250 Vdc and 5 A maximum fused current.\u003c\/p\u003e\n\u003cp\u003eQ: What are the input voltage parameters for this termination assembly? A: It operates at a nominal input voltage of 24 Vdc, a maximum input voltage of 36 Vdc, and requires a relay pick-up voltage of at least 19.2 Vdc.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":66998501048435,"sku":"FS-TSRO-0824","price":88.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0644\/4348\/2227\/files\/MC-TDOY22_e6062916-f744-461b-bb0a-4581c3e98b5c.png?v=1792995236","url":"https:\/\/www.dcssupplier.com\/products\/honeywell-fs-tsro-0824-digital-output-field-termination-assembly","provider":"DcsSupplier Limited","version":"1.0","type":"link"}